Logo
Logo
Logo

Thermoventilation unit UTO SMALL, UTO-C1

Download HD image 07511633
CE logo

Thermoventilation unit UTO SMALL, UTO-C1

The UTO SMALL, UTO-C1 unit ventilator for horizontal ceiling-hung installation with rear intake, is the response to the growing market demand for ducted unit ventilators that are easy to install, also in combination with heat pumps, for ceiling-hung, ducted residential applications.
The units are 215 mm deep.
They can be connected to relevant ducting for distribution of the air inside the respective environments to be air conditioned.

The units are supplied ready for connection with a TAM-15 digital room thermostat (supplied separately), or with digital thermoregulation through the IdroLAN system to control the ambient temperature, fan speed, and operating mode.
The high-efficiency air-to-water round-tube plate-fin heat exchanger coil is made of copper tubing with louvred, high-efficiency aluminium fins, with the possibility for left-right rotation.
The coil connections are fitted with an anti-twist system, manual air vent valves and water draining valves.
Supplied standard with air intake/outlet plenum, and motorised 3-way valve kit for pre-assembled two-pipe system (composed of 3-way valve and NC electrothermal servo control, 230 Vac/50 Hz).

Moreover, thanks to the latest generation EC Brushless motor, with permanent magnets and direct current, equipped with control electronics (Inverter), continuous variation (from 0% to 100%) of the air flow rate and consequent modulation of the heating capacity, they respond to the growing demand for environmental comfort and allow significant energy savings, reducing consumption by up to 70% compared to traditional units with three-speed asynchronous motor.

Supplied standard with water connections on the left side.
Model Total Cooling Capacity [kW] med (min - m... Heating Capacity Prated,h [kW] med (min... Air flow rate [m³/h] med (min - max) Q.ty per pack. Code
Model UTO-25 C1
Total Cooling Capacity [kW] med (min - max) 2,40 (1,60 - 2,59)
Heating Capacity Prated,h [kW] med (min - max) 2,63 (1,71 - 2,85)
Air flow rate [m³/h] med (min - max) 435 (226 - 495)
Q.ty per pack. 1 pcs
Code 07511633
Model UTO-30 C1
Total Cooling Capacity [kW] med (min - max) 2,38 (1,78 - 3,09)
Heating Capacity Prated,h [kW] med (min - max) 2,52 (1,85 - 3,32)
Air flow rate [m³/h] med (min - max) 476 (302 - 724)
Q.ty per pack. 1 pcs
Code 07511643
Model UTO-35 C1
Total Cooling Capacity [kW] med (min - max) 2,70 (1,93 - 3,35)
Heating Capacity Prated,h [kW] med (min - max) 2,91 (2,04 - 3,67)
Air flow rate [m³/h] med (min - max) 511 (302 - 720)
Q.ty per pack. 1 pcs
Code 07511653
Model UTO-40 C1
Total Cooling Capacity [kW] med (min - max) 3,64 (2,40 - 4,02)
Heating Capacity Prated,h [kW] med (min - max) 3,85 (2,47 - 4,29)
Air flow rate [m³/h] med (min - max) 700 (360 - 830)
Q.ty per pack. 1 pcs
Code 07511663
Model UTO-45 C1
Total Cooling Capacity [kW] med (min - max) 4,23 (2,72 - 4,53)
Heating Capacity Prated,h [kW] med (min - max) 4,27 (2,67 - 4,59)
Air flow rate [m³/h] med (min - max) 735 (357 - 830)
Q.ty per pack. 1 pcs
Code 07511673
Cooling performance under the following standard nominal conditions:
- internal Air temperature = 27 (19) °C
- Water temperature = 7/12 °C
 
Heating performance under the following standard nominal conditions:
- internal Air temperature = 20 °C
- Water temperature = 45/40 °C
 
Information requirements for fancoils according to Regulation EU 2016/2281.
Performance according to EN 1397:2016, EN 16583:2015 standards.
 
Power supply: 230 Vac/1 ph/50 Hz.
 
Standard water connection on the left side.