Mixing Unit M3V

Download HD image 28158340
ErP

Mixing Unit M3V

M3V HE-V with electronic circulator is the ideal solution for both independent and centralised mixed systems (radiant panels + radiators/fan coil units): in this case, the advantages of a centralised system are perfectly combined with the convenience of a climate control system independently managed at each usage point.

The mixing system allows the accurate balancing of the low temperature system in accordance with the design specifications, with either a thermostatic head for fixed-point control (heating only), or an electric servomotor for climate control (heating and/or cooling), reacting to any change in flow or heat emission and keeping the temperature of the fluid in the radiant panel system constant.
 
Technical data
- Max temperature on primary circuit: 90 °C
- Max operating pressure: 6 bar
- Δpmax on primary circuit: 1 bar
- Secondary regulation range (fixed-point regulation): 20 ÷ 65 °C
- Exchangeable heat output (with ΔT=7°C and Δp=0.25 bar): 11 kW with bypass in position 0, 14 kW with bypass in position 5
- Mixing valve pressure drops: Kv 2.5
- Kv with bypass valve in open position: max 6
- Topway manifold size: 1”
- Head thread: G 1” or 1"1/4, male
- Thermometer scale: 0 ÷ 80 °C

To be completed with:
- thermostatic head with immersion probe cod. 90046750
or
- 3-point electric servomotor cod. 28157212
or
- 0-10 V DC electric servomotor cod. 28157222
 
In case of installation of an electric servomotor, combine the RCE or PCOC electronic climatic regulation kit for heating and/or cooling.
Model Q.ty per pack. Code
Model 1"
Q.ty per pack. 1 pcs
Code 28158340
Model 1"1/4
Q.ty per pack. 1 pcs
Code 28158330
Code 28158340: threaded connections G 1" male. Article also compatible with Topway brass manifolds, by replacing the 4 red O-rings fitted as standard with the 4 black O-rings supplied in the pack.
 
Code 28158330: threaded connections G 1"1/4 male.