TM3-R without manifolds and pump
Download HD imageTM3-R without manifolds and pump
TM3-R thermostatic mixer control unit with fixed-point regulation and thermostatic head, with functions allowing it to react to variations in flow or heat emission, keeping the temperature of the fluid in the radiant panel system constant.
Using the mixing system, the temperature of the supply water of the underfloor heating system (low temperature mixed water) is regulated at a fixed point, by means of the application on the mixing valve of a thermostatic head with a remote temperature sensor.
The capillary temperature sensor inserted in the immersion sleeve detects the temperature of the fluid downstream of the circulator, keeping it at the value set on the head knob.
By acting on the calibration and bypass valve, it is possible to adjust the bypass flow of the underfloor heating system, thus ensuring that the ΔT of the original design is reached.
The TM3-R mixing units can also operate with zero head, connected to an open manifold (hydraulic separator) or to a storage tank (puffer).
The unit comes complete with a thermostatic head with remote sensor for fixed-point regulation.
Technical specifications:
- Max temperature on primary circuit: 90 °C
- Max operating pressure: 6 bar
- Δp max on primary circuit: 1 bar
- Regulation range of thermostatic head: 20 ÷ 65 °C
-Exchangeable heat output (with ΔT=7°C and Δp=0.25 bar):
10 kW with bypass in position 0
12 kW with bypass in position 5
- Kv with bypass valve in position 5: 4.8
- Thermometer scale: 0 ÷ 80 °C
- Mixing unit head thread: G 1” Female
- Mixing unit manifold thread: G 1” Male
Using the mixing system, the temperature of the supply water of the underfloor heating system (low temperature mixed water) is regulated at a fixed point, by means of the application on the mixing valve of a thermostatic head with a remote temperature sensor.
The capillary temperature sensor inserted in the immersion sleeve detects the temperature of the fluid downstream of the circulator, keeping it at the value set on the head knob.
By acting on the calibration and bypass valve, it is possible to adjust the bypass flow of the underfloor heating system, thus ensuring that the ΔT of the original design is reached.
The TM3-R mixing units can also operate with zero head, connected to an open manifold (hydraulic separator) or to a storage tank (puffer).
The unit comes complete with a thermostatic head with remote sensor for fixed-point regulation.
Technical specifications:
- Max temperature on primary circuit: 90 °C
- Max operating pressure: 6 bar
- Δp max on primary circuit: 1 bar
- Regulation range of thermostatic head: 20 ÷ 65 °C
-Exchangeable heat output (with ΔT=7°C and Δp=0.25 bar):
10 kW with bypass in position 0
12 kW with bypass in position 5
- Kv with bypass valve in position 5: 4.8
- Thermometer scale: 0 ÷ 80 °C
- Mixing unit head thread: G 1” Female
- Mixing unit manifold thread: G 1” Male
Model | Q.ty per pack. | Code | |
---|---|---|---|
Model TM3-R without manifolds and pump | Q.ty per pack. 1 pcs | Code 28132200 |