Dew sensor for RCE temperature controller.
The dew sensor is used to detect the condensate on surfaces, such as the manifold through which the heat transfer fluid flows during cooling.
The sensor is connected to a digital input of the RCE temperature controller for mixing units, and when condensation is detected on the surface, it closes the contact, thus triggering the controller logic.

Up to 6 sensors can be connected to the controller in parallel.

Technical data
- Power supply: 15 Vdc ±10 %, max 10 mA
- Temperature limits: from 0 to 50 °C
- Humidity limits: from 0 to 100 % RH
- Trip level: 90-95 % RH
Model Q.ty per pack. Code
Model Dew sensor
Q.ty per pack. 1 pcs
Code 28139078