Single distribution group with predisposition for circulator pump.Low temperature.

Download HD image 28151804

Single distribution group with predisposition for circulator pump.Low temperature.

Single distribution module for low temperature heating systems with mixing valve, to manage zoned heating systems requiring large flows of water with consistent feed temperatures or mixed temperatures (high and low temperature for radiator/fan coil systems and radiant panels).
The main feature is the "modular" construction which allows to assemble one or more modules as required.
The mixing system with thermostatic head for fixed-point control (heating only), or with an electric servomotor for temperature control (heating and/or cooling), reacts to any change in flow or heat emission and keeps the temperature of the fluid of the radiant panel system constant.
The unit should be completed with the installation of a thermostatic head with a remote sensor (for fixed-point operation in heating mode only), or an electric servomotor (3-point floating, or 0-10 Vdc modulating) combined with a temperature controller for heating and/or cooling.

Can be facing upwards or downwards.
Delivered pre-assembled and facing downwards.
Complete with pipe union to be installed downstream of the circulator, 1"1/2 F flat face connection
To combine multiple adjacent modules, use the pair of fittings cod. 01301240.
Terminal closure is possible using no. 2 plugs cod. 90004830.

The system is composed of:
- open manifold
- low temperature distribution manifold
- mixing valves ready for thermostatic head or servomotor
- calibration and bypass valves
- Wilo PARA 25/7 electronic circulators
- monitoring thermometer
- lockshields
- manual air vent valve

Technical specifications:
- Distribution manifold head threads: 1”1/4 M - 1” F
- Distribution manifold outlet threads: nut 1” F
- Single zone outlet threads: 1” F
- Distribution manifold maximum temperature: 110 °C
- Maximum pressure: 10 bar
- Circulator connections: pipe union 1”1/2 - spacing 130 mm.

Technical specifications of low temperature mixing unit:
- Max temperature on primary circuit: 90 °C
- Max operating pressure: 10 bar
- Δpmax on primary circuit: 1 bar
- Exchangeable heat output (∆T 7 °C, ∆p effective 0.25 bar)
fixed-point regulation: 10 kW bypass pos.0
fixed-point regulation: 12.5 kW bypass pos. 5
- Mixing valve pressure drops (fixed-point regulation): Kv = 3
- Kv with bypass valve in open position: max 4.9

To be completed with:
- thermostatic head with immersion probe cod. 90046750
or
- 3-point electric servomotor cod. 28157212
or
- 0-10 V DC electric servomotor cod. 28157222
 
In case of installation of an electric servomotor, combine the RCE or PCOC electronic climatic regulation kit for heating and / or cooling.
Model Q.ty per pack. Code
Model 1L
Q.ty per pack. 1 pcs
Code 28151804